12-38
ET 200C Distributed I/O Station
EWA 4NEB 812 6119-02b
ET 200C Analog Output Module; AO 4
12 Bit (6ES7 145-0HF00-0XB0),
Continued
The table below shows the relationship between analog and digitized output
signals for the ranges of values:
"
10 V, 0 ... 10 V,
"
20 mA, 0 ... 20 mA,
4 ... 20 mA.
Table 12-32 Analog Output Signals of ET 200C; AO 4
12 Bit (Ranges of Values:
"
10 V, 0 ... 10 V,
"
20 mA,
0 ... 20 mA, 4 ... 20 mA)
Units
Measured value in mV
Digitized measured value
Range
0 ... 20
mA
4 ... 20
mA
"
20
mA
0 ... 10
V
1 ... 5
V
"
10V
15 1413 1211 10 9 8 7 6 5 4 3
1249
23.52
5.88
0 1 0 0 1 1 1 0 0 0 0 1 0
O
1204
23.52
:
23.52
11.758
:
11.758
0 1 0 0 1 0 1 1 0 1 0 0 0
Over-
load
:
:
:
:
:
:
:
:
load
range
1025
20.0195
20.016
20.2
10.0098
5.004
10.0098 0 1 0 0 0 0 0 0 0 0 0 1 0
range
1024
20.0
20.0
20.0
10.00
5.0
10.00
0 1 0 0 0 0 0 0 0 0 0 0 0
1023
19.98
19.98
19.98
9.99
4.995
9.990
0 0 1 1 1 1 1 1 1 1 1 1 1
512
10.0
12.0
10.0
5.00
3
5.000
0 0 1 0 0 0 0 0 0 0 0 0 0
256
5.0
8.00
5.0
2.50
2
2.500
0 0 0 1 0 0 0 0 0 0 0 0 0
1
0.0195
4.015
0.02
0.0098
1.00375
0.0098
0 0 0 0 0 0 0 0 0 0 0 0 1
Nom.
range
0
0.0
4.0
0.0
0.0
1.0
0.000
0 0 0 0 0 0 0 0 0 0 0 0 0
range
–1
0.0
3.984
–0.02
0.0
0.996
–0.0098 1 1 1 1 1 1 1 1 1 1 1 1 1
–256
0.0
0.0
–05.0
0.0
0.0
–2.500
1 1 1 1 0 0 0 0 0 0 0 0 0
–512
0.0
0.0
–10.0
0.0
0.0
–5.000
1 1 1 0 0 0 0 0 0 0 0 0 0
–1024
0.0
0.0
–20.00
0.0
0.0
–10.000 1 1 0 0 0 0 0 0 0 0 0 0 0
–1025
0.0
0.0
–20.02
0.0
0.0
–10.009 1 0 1 1 1 1 1 1 1 1 1 1 1
Over-
:
:
:
:
:
:
:
:
Over
load
–1204
0.0
0.0
–23.52
0.0
0.0
–11.758 1 0 1 1 0 1 0 0 1 1 1 0 0
range
Table of Measured
Values
Analog Modules
Summary of Contents for SIMATIC ET 200C
Page 18: ...xviii ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Contents ...
Page 26: ...1 8 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Configuration ...
Page 44: ...2 18 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b ET 200C Configuration Options ...
Page 68: ...3 24 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b ET 200C Components ...
Page 202: ...10 4 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b General Technical Specifications ...
Page 226: ...11 24 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Digital Modules ...
Page 270: ...12 44 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Analog Modules ...
Page 280: ...13 10 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Other ET 200C Components ...