12-33
ET 200C Distributed I/O Station
EWA 4NEB 812 6119-02b
12.3 ET 200C Analog Output Module; AO 4
12 Bit
(6ES7 145-0HF00-0XB0)
Technical Data
Transfer rates
9.6/19.2/93.75/187.5/
500/1500 kbaud
Bus protocol
DP standard
Galvanically isolated from
SINEC L2-DP bus
yes
Power loss
typ. 3.0 W
Weight
approx. 950 g
Dimensions (W
H
D)
200
100
57
Diagnostics Functions
Voltage monitoring
green LED “RUN”
SINEC L2-DP bus
monitoring
red LED “BF”
Group diagnostics
red LED “DIA”,
parameterizable
Supply Voltage Outputs and Internal Logic
Supply voltage (L+)
Nominal
24 V DC
Permissible range
20.4 ... 30.2 V
Value for t < 0.5 s
35 V
Current consumption from L+
Logic
120 mA
Outputs
Number of outputs
4
Galvanic isolation between
voltage supply and internal
logic
yes
Test voltage
500 V DC
Measured value ranges
Voltage range
"
10 V, 0– 10 V,
1 – 5 V
Current range
"
20 mA, 0 – 20 mA,
4 – 20 mA
Connection
four- or two-wire
Load resistance
Voltage output
min.
1
k
W
Load impedance for
voltage output
max. 500
W
Capacitive load
max.
1 m
F
Inductive load
max. 1 m
H
Measured value presentation
12 bit + sign
Overload range
approx. 17.5 %
Conversion time
S5:
max. 2 ms per output
Outputs (Continued)
Conversion time
S7:
max. 1 ms per output
Settling time
for ohmic load
0.15 ms
for capacitive load
2.5 ms
for inductive load
0.2 ms
Permissible potential
differential
M
A
to PE or M
max. 75 V DC/60 V AC
Crosstalk between outputs
40 dB
Operational limit (for entire
temperature range, referenced
to output range)
Voltage
"
0.5 %
Current
"
0.6 %
Basic error (operational limit
at 25
C, referenced to output
range)
Voltage
"
0.3 %
Current
"
0.4 %
Temperature error (referenced
to output range)
"
0.02 %/K
Linearity error (referenced to
output range)
"
0.05 %
Repeat accuracy (in steady
state at 25
C, referenced to
output range)
"
0.05 %
Output ripple (referenced to
output range)
"
0.10 %
Voltage output
Short-circuit protection
yes, max. 1 output
simultaneously
Short-circuit current
max. 25 mA
Current output
No-load voltage
max. 18 V
Cable length
shielded
max. 30 m
Substitute values
yes, parameterizable
Diagnostics alarm
yes, parameterizable
Diagnostics information
accessible
yes
Analog Modules
Summary of Contents for SIMATIC ET 200C
Page 18: ...xviii ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Contents ...
Page 26: ...1 8 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Configuration ...
Page 44: ...2 18 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b ET 200C Configuration Options ...
Page 68: ...3 24 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b ET 200C Components ...
Page 202: ...10 4 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b General Technical Specifications ...
Page 226: ...11 24 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Digital Modules ...
Page 270: ...12 44 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Analog Modules ...
Page 280: ...13 10 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Other ET 200C Components ...
Page 310: ...C 4 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Safety Related Guidelines ...
Page 318: ...Glossary 8 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Glossary ...
Page 324: ...Index 6 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Index ...