5-12
ET 200C Distributed I/O Station
EWA 4NEB 812 6119-02b
5.1.4
Enter Parameterization Frame with COM ET 200 V4.x
The diagnostic behavior of each individual input or output or the entire mod-
ule (16 DI/16 DO) is defined for the digital ET 200C modules using the
parameterization frame.
Note
The diagnostics function must always be switched off for an input/output,
S
if the output is not used or
S
if an output is returned directly to an input or
S
if the sensor supply of an input is returned directly to the input
(see Section 4.3.2/4.3.3).
Perform the following steps in order to enter the diagnostic behavior in the
parameterization frame of the ET 200C:
1. Press (shift) F6 (DP slave parameterization frame).
The ”DP slave parameterization frame” window for the ET 200C station
will then appear. 5 bytes of the parameterization frame are preassigned
with ”00
H
” the first time this is selected:
DP SLAVE - PARAMETERIZATION FRAME
Byte
(entry in format KH)
–––––––––––––––––––––––––––––––––––––––––––––––
0
00
00
00
00
00
10
20
2. Then enter the diagnostic behavior of the ET 200C station in the format
”KH”.
Note
Only bytes 0 and 1 (marked with ”
j
” in the diagram) are relevant for
parameterizing the diagnostic behavior of the ET 200C station . The entry
options and their meaning are described in Fig. 5-5 and 5-4.
Bytes 2, 3 and 4 contain ”00
H
” which cannot be overwritten!
3. Terminate the entry with <F6> (ENTER).
4. Confirm the configuration with <F6> (ENTER).
Introduction
Procedure: Define
Diagnostic
behavior
Address Assignment and Parameterization with COM ET 200
Summary of Contents for SIMATIC ET 200C
Page 18: ...xviii ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Contents ...
Page 26: ...1 8 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Configuration ...
Page 44: ...2 18 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b ET 200C Configuration Options ...
Page 68: ...3 24 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b ET 200C Components ...
Page 202: ...10 4 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b General Technical Specifications ...
Page 226: ...11 24 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Digital Modules ...
Page 270: ...12 44 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Analog Modules ...
Page 280: ...13 10 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Other ET 200C Components ...
Page 310: ...C 4 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Safety Related Guidelines ...
Page 318: ...Glossary 8 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Glossary ...
Page 324: ...Index 6 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Index ...