4-12
ET 200C Distributed I/O Station
EWA 4NEB 812 6119-02b
Wiring of the Bus Connection, Continued
If you only wish to connect the power supply, you require
12-pin circular connectors
3-core cable with a diameter of 6 to 10 mm.
Connect the circular connectors in accordance with the following table:
Table 4-4
Pin Assignment of the Bus Connection where only the Power Supply is
Connected
Pin
Assignment
Pin
Assignment
1
reserved
7
P 24 V
2
reserved
8
M 24 V
3
reserved
9
PE
4
reserved
10
reserved
5
reserved
11
reserved
6
reserved
12
reserved
If you combine the SINEC L2-DP bus and the power supply in a single cable,
you will require
12-pin circular plugs
5-core cable with a diameter of 6 to 10 mm.
Table 4-5
Pin Assignment of the Bus Connection if SINEC L2-DP and Power
Supply are Connected
Pin
Assignment
Pin
Assignment
1
reserved
7
P 24 V
2
A (green)
8
M 24 V
3
reserved
9
PE
4
B (red)
10
reserved
5
reserved
11
reserved
6
reserved
12
reserved
Connections which are not required must be sealed using the enclosed metal
caps.
Connecting only
power supply
Connecting
SINEC L2-DP and
Power Supply
Sealing of Unused
Connections
Mechanical and Electrical Installation
Summary of Contents for SIMATIC ET 200C
Page 18: ...xviii ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Contents ...
Page 26: ...1 8 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Configuration ...
Page 44: ...2 18 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b ET 200C Configuration Options ...
Page 68: ...3 24 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b ET 200C Components ...
Page 202: ...10 4 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b General Technical Specifications ...
Page 226: ...11 24 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Digital Modules ...
Page 270: ...12 44 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Analog Modules ...
Page 280: ...13 10 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Other ET 200C Components ...
Page 310: ...C 4 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Safety Related Guidelines ...
Page 318: ...Glossary 8 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Glossary ...
Page 324: ...Index 6 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Index ...