12-11
ET 200C Distributed I/O Station
EWA 4NEB 812 6119-02b
The three tables below contain the relationships between analog and digitized
measured values for thermocouples of types K, J and L.
Table 12-7
Digitized Measured Values for ET 200C; AI 4/8
12 Bit with Linearization; Type K Thermocouple
(Nickel-Chromium/Nickel-Aluminum, to IEC 584)
Units
Thermal
e.m.f. in
Temperature
in
°
C
Digitized measured value
X F O
Range
e.m.f. in
mV
1
in C
15 14 13 12 11 10 9 8
7 6
5 4 3 2 1 0
> 2359
0 1 0 0 1 0 0 1 1 0 1 1 1 0 0 1
Overflow
1370
1370
0 0 1 0 1 0 1 0 1 1 0 1 0 0 0 0
Overload range
2
1369
54.773
1369
0 0 1 0 1 0 1 0 1 1 0 0 1 0 0 0
1000
41.269
1000
0 0 0 1 1 1 1 1 0 1 0 0 0 0 0 0
500
20.640
500
0 0 0 0 1 1 1 1 1 0 1 0 0 0 0 0
150
6.137
150
0 0 0 0 0 1 0 0 1 0 1 1 0 0 0 0
Nominal range
100
4.095
100
0 0 0 0 0 0 1 1 0 0 1 0 0 0 0 0
1
0.039
1
0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 0
0
0
0
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
–1
–0.039
–1
1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0
–100
–3.553
–100
1 1 1 1 1 1 0 0 1 1 1 0 0 0 0 0
–101
–3.584
–101
1 1 1 1 1 1 0 0 1 1 0 1 1 0 0 0
Precision
–150
–4.912
–150
1 1 1 1 1 0 1 1 0 1 0 1 0 0 0 0
v
2 K
–200
–5.891
–200
1 1 1 1 1 0 0 1 1 1 0 0 0 0 0 0
–201
–201
1 1 1 1 1 0 0 1 1 0 1 1 1 0 0 0
Overload range
2
–273
1 1 1 1 0 0 0 0 1 0 0 1 0 0 0 1
Overflow
X
X
X X X X X X X X X X X X X 0 1 0
Wire break
1
For a reference temperature 0
°
C
2
In the overload range, the characteristic retains the angle adopted on leaving the linearized nominal range.
Table of Measured
Values
Analog Modules
Summary of Contents for SIMATIC ET 200C
Page 18: ...xviii ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Contents ...
Page 26: ...1 8 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Configuration ...
Page 44: ...2 18 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b ET 200C Configuration Options ...
Page 68: ...3 24 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b ET 200C Components ...
Page 202: ...10 4 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b General Technical Specifications ...
Page 226: ...11 24 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Digital Modules ...
Page 270: ...12 44 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Analog Modules ...
Page 280: ...13 10 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Other ET 200C Components ...
Page 310: ...C 4 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Safety Related Guidelines ...
Page 318: ...Glossary 8 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Glossary ...
Page 324: ...Index 6 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Index ...