4-13
ET 200C Distributed I/O Station
EWA 4NEB 812 6119-02b
4.3.2
Wiring of ET 200C; DI 8
DC 24V (6ES7 141-0BF00-0XB0)
To wire the inputs you will require
5-pin circular plugs
Flexible 4-core Cu cables with a minimum core cross-section of
0.75 mm
2
.
Connect the inputs in accordance with the pin assignment in the following
table.
Table 4-6
Pin Assignment of the Inputs of ET 200C; DI 8
DC 24V
(6ES7 141-0BF00-0XB0)
Pin
Input
View
1
24 V DC
1
1 2
2
Free
1 2
5
3
Ground
3
4
5
4
Signal
View: Mating Side
3
4
5
PE
View: Mating Side
1
The module supplies this 24 V DC at pin 1 as the voltage supply for the connected
sensors.
Inputs which are not required must be sealed using the enclosed twist caps.
Connecting Inputs
Sealing of Unused
Inputs
Mechanical and Electrical Installation
Summary of Contents for SIMATIC ET 200C
Page 18: ...xviii ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Contents ...
Page 26: ...1 8 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Configuration ...
Page 44: ...2 18 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b ET 200C Configuration Options ...
Page 68: ...3 24 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b ET 200C Components ...
Page 202: ...10 4 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b General Technical Specifications ...
Page 226: ...11 24 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Digital Modules ...
Page 270: ...12 44 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Analog Modules ...
Page 280: ...13 10 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Other ET 200C Components ...
Page 310: ...C 4 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Safety Related Guidelines ...
Page 318: ...Glossary 8 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Glossary ...
Page 324: ...Index 6 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Index ...