11-6
ET 200C Distributed I/O Station
EWA 4NEB 812 6119-02b
11.2
Digital Output Module ET 200C; DO 8
DC 24V/0.5A
(6ES7 142-0BF00-0XB0)
Technical Specifications
Baud rates
9.6/19.2/93.75/187.5/500/
1500/3000
1
/6000
1
/
12000
1
kbaud
Mains buffering (without
sensor and load voltage
supply)
typ. 20 ms
Insulation rating
to VDE 0160
Nominal insulation voltage
(L+ against PE)
60 V AC (75 V DC)
Test voltage
500 V DC
Electrical isolation to
SINEC L2-DP bus
500 V
Power loss
typ. 4.1 W
Weight
approx. 1000 g
Dimensions (W
H
D)
223
100
57
Diagnostic Functions
Voltage monitoring
green LED “RUN”
SINEC L2-DP bus
monitoring
red LED “BF”
Group diagnostics for
shortcircuit, overload or
wire break
red LED “DIA”
Status of outputs
red LED for individual
diagnostics (short-circuit
or wire break of outputs)
8 red LEDs for supply
undervoltage or internal fuse
4 red LEDs for internal fuse
green LED for status of
outputs
Voltage supply of outputs
green LED “U
L
” supply of
outputs
1
This baud rate is only relevant in conjunction with the
IM 308-C.
Supply Voltage for Outputs, Load Voltage Supply
and Internal Logic
Nominal value (L+)
24 V DC
Permissible range
(incl. ripple = max. 3.6 V)
20 to 30 V
Value at t < 0.5 s
35 V
Short-circuit capability
Yes
Current consumption
Logic
Load
typ. 90 mA
typ. 80 mA
Short-circuit current
max. 4 A
Outputs
Number of outputs
8
Connection
via 5-pin circular connectors
3-wire connection per
channel
Electrical isolation between
internal logic and outputs
Yes, 500 V
Load voltage supply
Nominal value (L1)
Permissible range (incl.
ripple = max. 3.6 V)
24 V DC
20 to 30 V
Output current for “1”
signal
Nominal value
Permissible range
Lamp load
500 mA per channel
0 to 500 mA per channel
max. 5 W
Permissible total current
4 A
Residual current for “0”
signal
max. 0.3 mA
Wire break recognition
No wire break recognition
typ. I
v
1 mA
typ. I
w
10 mA
Short-circuit diagnostics
signal
typ. 1 A
Switching frequency
at resistive load
at inductive load
100 Hz
0.5 Hz
Limitation of voltage in-
duced on circuit interruption
typ. (L+) – 50 V
Cable length of outputs
max. 50 m
Digital Modules
Summary of Contents for SIMATIC ET 200C
Page 18: ...xviii ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Contents ...
Page 26: ...1 8 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Configuration ...
Page 44: ...2 18 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b ET 200C Configuration Options ...
Page 68: ...3 24 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b ET 200C Components ...
Page 202: ...10 4 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b General Technical Specifications ...
Page 226: ...11 24 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Digital Modules ...
Page 270: ...12 44 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Analog Modules ...
Page 280: ...13 10 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Other ET 200C Components ...
Page 310: ...C 4 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Safety Related Guidelines ...
Page 318: ...Glossary 8 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Glossary ...
Page 324: ...Index 6 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Index ...