12-12
ET 200C Distributed I/O Station
EWA 4NEB 812 6119-02b
ET 200C Analog Input Module; AI 4/8
12 Bit (6ES7 144-0KH00-0XB0),
Continued
Table 12-8
Digitized Measured Values for ET 200C; AI 4/8
12 Bit with Linearization; Type J Thermocouple
(Iron/Copper-Nickel (Constantan), to IEC 584)
Units
Thermal
e.m.f. in
Temperature
in
°
C
Digitized measured value
X F O
Range
e.m.f. in
mV
1
in C
15 14 13 12 11 10 9 8
7 6
5 4 3 2 1 0
1485
0 0 1 0 1 1 1 0 0 1 1 0 1 0 0 1
Overflow
1201
1201
0 0 1 0 0 1 0 1 1 0 0 0 1 0 0 0
Overload range
2
1200
69.536
1200
0 0 1 0 0 1 0 1 1 0 0 0 0 0 0 0
1000
57.942
1000
0 0 0 1 1 1 1 1 0 1 0 0 0 0 0 0
500
27.388
500
0 0 0 0 1 1 1 1 1 0 1 0 0 0 0 0
100
5.268
100
0 0 0 0 0 0 1 1 0 0 1 0 0 0 0 0
1
0.05
1
0 0 0 0 0 0 0 0 0 0 0 0 1 0 0 0
Nominal range
0
0
0
0 0 0 0 0 0 0 0 0 0 0 0 0 0 0 0
–1
–0.05
–1
1 1 1 1 1 1 1 1 1 1 1 1 1 0 0 0
–100
–4.632
–100
1 1 1 1 1 1 0 0 1 1 1 0 0 0 0 0
–150
–6.499
–150
1 1 1 1 1 0 1 1 0 1 0 1 0 0 0 0
–199
–7.868
–199
1 1 1 1 1 0 0 1 1 1 0 0 1 0 0 0
–200
–7.890
–200
1 1 1 1 1 0 0 1 1 1 0 0 0 0 0 0
–201
–201
1 1 1 1 1 0 0 1 1 0 1 1 1 0 0 0
Overload range
2
–273
1 1 1 1 0 1 1 1 0 1 1 1 1 0 0 1
Overflow
X
X
X X X X X X X X X X X X X 0 1 0
Wire break
1
For a reference temperature 0
°
C
2
In the overload range, the characteristic retains the angle adopted on leaving the linearized nominal range.
Analog Modules
Summary of Contents for SIMATIC ET 200C
Page 18: ...xviii ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Contents ...
Page 26: ...1 8 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Configuration ...
Page 44: ...2 18 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b ET 200C Configuration Options ...
Page 68: ...3 24 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b ET 200C Components ...
Page 202: ...10 4 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b General Technical Specifications ...
Page 226: ...11 24 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Digital Modules ...
Page 270: ...12 44 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Analog Modules ...
Page 280: ...13 10 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Other ET 200C Components ...
Page 310: ...C 4 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Safety Related Guidelines ...
Page 318: ...Glossary 8 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Glossary ...
Page 324: ...Index 6 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Index ...