7-4
ET 200C Distributed I/O Station
EWA 4NEB 812 6119-02b
Using LEDs to Diagnose Problems, Continued
Table 7-3
Fault Messages through LEDs of the ET 200C; DI 16/DO 16
DC 24V/2A
LED
Optical Signal
Explanation
RUN
Lit (green)
ET 200C; DI 16/DO 16
DC 24V/2A is in the
RUN mode (power supply switched on)
U
L1
Lit (green)
Load voltage for channel group Q0 present
U
L2
Lit (green)
Load voltage for channel group Q1 present
BF
Lit (red)
Either
The monitoring time has elapsed without the
ET 200C; DI 16/DO 16
DC 24V/2A being
addressed (because the connection to the
IM 308-B is lost or IM 308-B is in STOP mode)
or
ET 200C; DI 16/DO 16
DC 24V/2A was not
parameterized during startup or a restart
DIA
Lit (red)
Group diagnostics for groups of 4 inputs or 4 out-
puts:
Inputs: wire break, short-circuit
1
/overload of the
sensor supply
Outputs: wire break, short-circuit
2
/overload or
undervoltage at the outputs
0, 1, 2, 3, 4, 5, 6, 7, 8,
9,10,11,12,13,14,15
Lit (green)
Input or output active
(Status LEDs of the
inputs/outputs)
1
The sensor supply for all of the inputs in the group of 4 is interrupted in the event of a short-circuit in the sensor supply.
2
The diagnostics message remains for a further 20 s (approx.) after the short-circuit has been eliminated (e.g. when an
output is reset).
Fault Diagnostics with the IM 308-B
Summary of Contents for SIMATIC ET 200C
Page 18: ...xviii ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Contents ...
Page 26: ...1 8 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Configuration ...
Page 44: ...2 18 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b ET 200C Configuration Options ...
Page 68: ...3 24 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b ET 200C Components ...
Page 202: ...10 4 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b General Technical Specifications ...
Page 226: ...11 24 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Digital Modules ...
Page 270: ...12 44 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Analog Modules ...
Page 280: ...13 10 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Other ET 200C Components ...
Page 310: ...C 4 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Safety Related Guidelines ...
Page 318: ...Glossary 8 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Glossary ...
Page 324: ...Index 6 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Index ...