The rules which apply to setting the station number by means of the DIL
switches in DIL switch block S1 are as follows:
The single DIL switch of DIL switch block S1 must be set to M (for
Manual setting via DIL switch). The default setting of this switch is E
(for Electronic setting via the bus).
An ET 200C analog module must be assigned a station number in the
range:
–
IM 308-B master interface: 3 ... 124
–
IM 308-C master interface: 1 ... 123
You must also enter the same station number when parameterizing with
COM ET 200.
Example
You want to assign station number 6 to an analog module
6
=
2 + 4
DIL switch block S1 set to station number 6
64
32
16
8
4
2
1
S1
M
E
1
0
Figure 4-29
Example of How to Set a Station Number at DIL Switch Block S1
To set a station number by means of the DIL switches in DIL switch block
S1, proceed as follows:
1. Open the analog module.
2. On the lower printed-circuit board, set the single switch of DIL switch
block S1 to M (for Manual).
3. Set the station number by means of the block of seven DIL switches (see
Figure 4-29).
4. Close the module, making sure that the cover is correctly seated as
damage may occur if the cover is not aligned with the casing.
Rules
Setting a Station
Number by Means
of DIL Switches
Mechanical and Electrical Installation
Summary of Contents for SIMATIC ET 200C
Page 18: ...xviii ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Contents ...
Page 26: ...1 8 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Configuration ...
Page 44: ...2 18 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b ET 200C Configuration Options ...
Page 68: ...3 24 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b ET 200C Components ...
Page 202: ...10 4 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b General Technical Specifications ...
Page 226: ...11 24 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Digital Modules ...
Page 270: ...12 44 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Analog Modules ...
Page 280: ...13 10 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Other ET 200C Components ...
Page 310: ...C 4 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Safety Related Guidelines ...
Page 318: ...Glossary 8 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Glossary ...
Page 324: ...Index 6 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Index ...