6-6
ET 200C Distributed I/O Station
EWA 4NEB 812 6119-02b
6.3
Testing the ET 200C Distributed I/O Station
Once you have parameterized your ET 200C station (see Section 6.2),
COM ET 200 V4.x automatically goes to the ”STARTUP/TEST: STATUS/
CONTROL” form.
The slot of the input/output port is selected as follows:
1. Position the cursor at the slot of the ET 200C, the input status of which
you wish to evaluate or the outputs of which you wish to control.
2. Press <F5> (SELECT.).
Result:
The selected slot is marked with a ”*”. The slot will be deselected if
<F5> (SELECT.) is pressed again.
3. Confirm the selection with <F6> (ENTER).
The ”SYSTEM START-UP/TEST: STATUS/CONTROL” screen for the se-
lected station appears with the following contents:
Diagnostics messages for the entire station appear in plain text in the
output field ”Station status”.
The digital inputs/outputs are displayed in ”KH” format in two tables.
Note on changing the baud rate:
Note
It is possible that the ET 200C station will not be admitted to the
SINEC L2-DP bus when an incorrect configuration is redefined and the baud
rate is changed at the same time.
Basic Requirement
Procedure:
Select Slot
Result
Changing the
Baud Rate
Startup and Test with COM ET 200
Summary of Contents for SIMATIC ET 200C
Page 18: ...xviii ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Contents ...
Page 26: ...1 8 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Configuration ...
Page 44: ...2 18 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b ET 200C Configuration Options ...
Page 68: ...3 24 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b ET 200C Components ...
Page 202: ...10 4 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b General Technical Specifications ...
Page 226: ...11 24 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Digital Modules ...
Page 270: ...12 44 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Analog Modules ...
Page 280: ...13 10 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Other ET 200C Components ...
Page 310: ...C 4 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Safety Related Guidelines ...
Page 318: ...Glossary 8 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Glossary ...
Page 324: ...Index 6 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Index ...