5-3
ET 200C Distributed I/O Station
EWA 4NEB 812 6119-02b
5.1.1
Enter Station Number
You have processed the ET 200 system parameters in the COM ET 200 form
”ET 200 SYSTEM PARAMETERS” (see the manual ET 200 Distributed I/O
System).
Please note the following when editing the station number:
An ET 200C station must have a station number between 3 and 124.
The station number of a “further active station” (if specified in the
“ET 200 SYSTEM PARAMETERS” form) may not be entered for the
ET 200C station!
The station number is entered as follows:
1. From the “FUNCTION SELECTION” screen, press <F2> to go to the
“CONFIGURING” screen.
2. If necessary, correct the station number that appears on the screen.
Entry options:
Possible station numbers for ET 200C: 3 to 124
Help:
Press <F7> (HELP). A window appears with all previously assigned
station numbers and station types. You can select a station and display its
configuration. If no station number has been assigned, the message
“
No stations configured
” appears.
3. Confirm the entry with <F6> (ENTER).
If the station whose number you entered has already been configured, its con-
figuration appears on the screen after you complete your entry.
If the station whose number you entered has not already been configured,
two additional entry fields appear in the “CONFIGURING” screen: “Area”
and “Station type”
(see Section 5.1.2).
Basic Requirement
Rules
Procedure:
Enter Station
Number
Result
Address Assignment and Parameterization with COM ET 200
Summary of Contents for SIMATIC ET 200C
Page 18: ...xviii ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Contents ...
Page 26: ...1 8 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Configuration ...
Page 44: ...2 18 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b ET 200C Configuration Options ...
Page 68: ...3 24 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b ET 200C Components ...
Page 202: ...10 4 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b General Technical Specifications ...
Page 226: ...11 24 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Digital Modules ...
Page 270: ...12 44 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Analog Modules ...
Page 280: ...13 10 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Other ET 200C Components ...
Page 310: ...C 4 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Safety Related Guidelines ...
Page 318: ...Glossary 8 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Glossary ...
Page 324: ...Index 6 ET 200C Distributed I O Station EWA 4NEB 812 6119 02b Index ...