Commissioning
6.3 Parameterizing the device
68
Equipment Manual, 09/2022, L1V30415168B-03
Selection
Range
Factory
setting
Usage type
Not used:
Digital input is deactivated.
Input pulse count:
Counting of input pulses.
Note:
The universal counter must also be parameterized for pulse
counting. Set the parameter "Advanced > Universal Counter" to
"Digital Input".
High tariff/low tariff switchover:
Switching between tariffs: Off-peak tariff if input active
Demand synchronization:
Synchronization of power demand
Not used
Unit
(only for: input
pulse counter)
Countable unit with pulse counting:
•
Active Energy (kWh)
•
Reactive Energy (kvarh)
—
Pulses per unit
(only for: input
pulse counter)
Number of pulses that must be received per unit in order for the
counter to be incremented by "1".
Range:
1 ... 4000
The reference unit is defined in the "UNIT" field.
1
Input pulse
divider
1)
Range:
1; 10; 100; 1000
1) Formula:
Example:
Pulses per unit: 50
Pulse divider: 100
Unit: kWh