Appendix
A.1 Modbus TCP
Equipment Manual, 09/2022, L1V30415168B-03
123
Table A- 8
Settings parameter for the digital input
Offset
Number of
registers
Name
Unit
Format
Value range
Access
50025
2
Digital input "Action" —
Unsigned long 0 =
Status only
RW
1 =
Pulse input
2 =
On-peak/off-peak tariff
switching
3 =
Synchronization
50029
2
"Pulse input" mode
—
Unsigned long 0 =
0 kWh
RW
1 =
Export kWh
50031
2
Pulses per unit (pulses
per 1000 Wh / VARh)
—
Unsigned long 1 ... 999
RW
50239
2
Input pulse divider
—
Unsigned long 0 =
1 kWh
RW
1 =
10 kWh
2 =
100 kWh
3 =
1000 kWh