
Connection
4.3 Connection examples
Equipment Manual, 09/2022, L1V30415168B-03
41
(11) Two-phase measurement, three conductors, unbalanced load, without voltage
transformer, with two current transformers
Connection type 3P4W
*
The fuses are only used for cable protection. All commercially available fuses and automatic
circuit breakers up to 16 A (C) or 20 A (B) can be used.
**
Install a short-circuit device. Protection against overvoltage when the secondary transformer
circuit is open.
Figure 4-12 Connection type 3P4W, without voltage transformer, with two current transformers
The device indicates 0 (zero) V for L3.
(12) Single-phase measurement, two conductors, without voltage transformer, with one
current transformer
Connection type 1P2W
*
The fuses are only used for cable protection. All commercially available fuses and automatic
circuit breakers up to 16 A (C) or 20 A (B) can be used.
**
Install a short-circuit device. Protection against overvoltage when the secondary transformer
circuit is open.
Figure 4-13 Connection type 1P2W, without voltage transformer, with one current transformer
Summary of Contents for SENTRON PAC3200T
Page 1: ......
Page 2: ......
Page 8: ......
Page 14: ......
Page 30: ......
Page 46: ......
Page 54: ......
Page 74: ......
Page 88: ......
Page 89: ...Equipment Manual 09 2022 L1V30415168B 03 87 Dimensional drawings 9 Frame dimensions ...
Page 90: ......
Page 134: ...Equipment Manual 09 2022 L1V30415168B 03 132 ...
Page 135: ......
Page 136: ......