Description
2.2 Measuring inputs
16
Equipment Manual, 09/2022, L1V30415168B-03
Connection types
Five connection types have been provided. The device can measure in single-phase, two-
phase, or three-phase mode and can be used in three- or four-wire TN, TT and IT networks.
Table 2- 1
Available connection types
Short code
Connection type
3P4W (factory setting)
3 phases, 4 conductors, unbalanced load
3P3W
3 phases, 3 conductors, unbalanced load
3P4WB
3 phases, 4 conductors, balanced load
3P3WB
3 phases, 3 conductors, balanced load
1P2W
1 phase, 2 conductors, unbalanced load
The input circuit of the device must correspond to one of the connection types listed. Select
the suitable connection type for the purpose.
You can find connection examples in the chapter Connection (Page 31).
NOTICE
The wrong system connection can damage the device.
Before connecting the PAC3200T, ensure that the local power supply conditions match the
specifications on the type plate.
The short code of the connection type must be entered in the device settings at startup. You
can find the instructions for parameterizing the connection type in the chapter
Commissioning (Page 53).
Measured variables that can be read out depending on the connection type
The table below shows which measured variables can be read out, depending on the
connection type.
Table 2- 2
Measured variables depending on the connection type
Connection type
Measured variable
Avail.
3P4W
Avail.
3P3W
Avail.
3P4WB
Avail.
3P3WB
Avail.
1P2W
Voltage L
1-N
✓
—
✓
—
✓
Voltage L
2-N
✓
—
—
—
—
Voltage L
3-N
✓
—
—
—
—
Voltage L
1-2
✓
✓
✓
✓
—
Voltage L
2-3
✓
✓
✓
✓
—
Voltage L
3-1
✓
✓
✓
✓
—
Current L
1
✓
✓
✓
✓
✓
Current L
2
✓
✓
—
—
—
Current L
3
✓
✓
—
—
—
Neutral current
✓
—
✓
—
✓
Apparent power L
1
✓
—
✓
—
✓
Summary of Contents for SENTRON PAC3200T
Page 1: ......
Page 2: ......
Page 8: ......
Page 14: ......
Page 30: ......
Page 46: ......
Page 54: ......
Page 74: ......
Page 88: ......
Page 89: ...Equipment Manual 09 2022 L1V30415168B 03 87 Dimensional drawings 9 Frame dimensions ...
Page 90: ......
Page 134: ...Equipment Manual 09 2022 L1V30415168B 03 132 ...
Page 135: ......
Page 136: ......