
Connection
4.3 Connection examples
38
Equipment Manual, 09/2022, L1V30415168B-03
(5) Three-phase measurement, three conductors, unbalanced load, without voltage
transformer, with three current transformers
Connection type 3P3W
*
The fuses are only used for cable protection. All commercially available fuses and automatic
circuit breakers up to 16 A (C) or 20 A (B) can be used.
**
Install a short-circuit device. Protection against overvoltage when the secondary transformer
circuit is open.
Figure 4-6
Connection type 3P3W, without voltage transformer, with three current transformers
(6) Three-phase measurement, three conductors, unbalanced load, with voltage
transformer, with three current transformers
Connection type 3P3W
*
The fuses are only used for cable protection. All commercially available fuses and automatic
circuit breakers up to 16 A (C) or 20 A (B) can be used.
**
Install a short-circuit device. Protection against overvoltage when the secondary transformer
circuit is open.
Figure 4-7
Connection type 3P3W, with voltage transformer, with three current transformers
Summary of Contents for SENTRON PAC3200T
Page 1: ......
Page 2: ......
Page 8: ......
Page 14: ......
Page 30: ......
Page 46: ......
Page 54: ......
Page 74: ......
Page 88: ......
Page 89: ...Equipment Manual 09 2022 L1V30415168B 03 87 Dimensional drawings 9 Frame dimensions ...
Page 90: ......
Page 134: ...Equipment Manual 09 2022 L1V30415168B 03 132 ...
Page 135: ......
Page 136: ......