Appendix
A.1 Modbus TCP
124
Equipment Manual, 09/2022, L1V30415168B-03
Table A- 9
Settings parameter for the digital output
Offset
Number of
registers
Name
Unit
Format
Value range
Access
50033
2
Switching function
assignment to a
vector group
—
Unsigned long 0 ... 99
RW
50035
2
Digital output "Action" —
Unsigned long 0 =
Off
RW
1 =
Device ON
2 =
Switching output
3 =
Rotation
4 =
Limit violation
5 =
Energy pulse
50037
2
"Limit violation" mode —
Unsigned long 0 =
Limit logic
RW
1 =
Limit 0
2 =
Limit 1
3 =
Limit 2
4 =
Limit 3
5 =
Limit 4
6 =
Limit 5
50041
2
"Energy pulse" mode
—
Unsigned long 0 =
Import kWh
RW
1 =
Export kWh
2 =
Import kVARh
3 =
Export kVARh
50043
2
Pulses per unit (pulses
per 1000 Wh / VARh)
—
Unsigned long 1 ... 4000
RW
50045
2
Pulse length
ms
Unsigned long 30 ... 500
RW
50147
2
Digital output timeout —
Unsigned long 0.1 ... 18000
RW
50237
2
Output pulse divider
—
Unsigned long 0 =
1 kWh
RW
1 =
10 kWh
2 =
100 kWh
3 =
1000 kWh