Commissioning
6.3 Parameterizing the device
66
Equipment Manual, 09/2022, L1V30415168B-03
Example:
LIM0, LIM1, LIM3 and LIM5 are to be linked to one another with the following logic:
Selection of the operators:
op0: AND (Λ)
op1: AND (Λ)
op2: ----
op3: AND (Λ)
op4: ----
op5: OR (V)
Formula:
(((((AND LIM0 AND LIM1) ---- LIM2) AND LIM3) ---- LIM4) OR LIM5) = RLO
Simplified representation: ((LIM0
Λ
LIM1)
Λ
LIM3) V LIM5 = RLO
"Universal Counter" parameter
The "Universal Counter" parameter is a configurable counter. It shows the source from which
status changes or limit violations are counted:
•
"Digital input" - Status changes at the digital input are counted (rising edge only).
•
"Digital output" - Status changes at the digital output are counted (rising edge only).
•
"Result Logic Array" - A violation of this limit value is counted.
•
"Limit 0" to "Limit 5" - A violation of this limit value is counted.