Appendix
A.1 Modbus TCP
122
Equipment Manual, 09/2022, L1V30415168B-03
A.1.10
Modbus settings with the function codes 0x03, 0x04 and 0x10
Addressing the settings
You can use the Modbus function codes 0x03 and 0x04 for read accesses and 0x10 for write
accesses on all the settings parameters listed below.
Table A- 7
Settings parameters
Offset
Number of
registers
Name
Unit
Format
Value range
Access
50001
2
Connection type
—
Unsigned long 0 =
3P4W
RW
1 =
3P3W
2 =
3P4WB
3 =
3P3WB
4 =
1P2W
50003
2
Voltage measurement
using voltage
transformers?
—
Unsigned long 0 =
No
RW
1 =
Yes
50005
2
Primary voltage
—
Unsigned long 1 ... 999999 V
RW
50007
2
Secondary voltage
—
Unsigned long 1 ... 690 V
RW
50011
2
Primary current
—
Unsigned long ... 99999 A
RW
50013
2
Secondary current
—
Unsigned long 1 A, 5 A
R
50019
2
Minimum current
(1% rated current)
%
Float
0.0 ... 10.0
RW
50021
2
Demand period
min
Unsigned long 1 ... 60
RW
50023
2
Synchronization
—
Unsigned long 0 =
No synchronization
RW
1 =
Synchronization via bus
2 =
Synchronization via the
digital input
50243
2
Change current L1
direction
—
Unsigned long 0 =
No
RW
1 =
Yes
50245
2
Change current L2
direction
—
Unsigned long 0 =
No
RW
1 =
Yes
50247
2
Change current L3
direction
—
Unsigned long 0 =
No
RW
1 =
Yes
Summary of Contents for SENTRON PAC3200T
Page 1: ......
Page 2: ......
Page 8: ......
Page 14: ......
Page 30: ......
Page 46: ......
Page 54: ......
Page 74: ......
Page 88: ......
Page 89: ...Equipment Manual 09 2022 L1V30415168B 03 87 Dimensional drawings 9 Frame dimensions ...
Page 90: ......
Page 134: ...Equipment Manual 09 2022 L1V30415168B 03 132 ...
Page 135: ......
Page 136: ......