A.5 EMC-compatible installation of electrical Industrial Ethernet or PROFIBUS cabling
SCALANCE X-300
Operating Instructions, 05/2016, A5E01113043-20
317
Radiated electromagnetic interference IEEE Std C37.90.2 35 V/m; 80 MHz to 1000 MHz
Damped oscillatory magnetic field IEC 60694, IEC 61000-4-12 2.5 kV (peak value), polarity
alternating 100 kHz, 1 MHz
EMC tests of emission (type tests)
Relevant standard: EN 61000-6-1 (generic standard)
Radiated emission on cables, only auxiliary voltage IEC-CISPR 22 150 kHz to 30 MHz limit
value class A
Radiated electric field strength IEC-CISPR 22, 30 MHz to 1000 MHz limit value class A
Voltage fluctuations and flicker on the power supply cable at 230 VAC IEC 61000-3-3; limit
values kept to.
A.5
EMC-compatible installation of electrical Industrial Ethernet or
PROFIBUS cabling
The Industrial Ethernet / PROFINET system manual "Passive network components"
prescribes the use of fiber-optic cables for cabling between buildings and/or external facilities
because there may be large potential differences between nodes.
If IE FC or PROFIBUS FC cables are used for such applications, the same rules apply as
when installing cables indoors.
The following also applies:
●
Install cables on metal cable racks
●
Electrically connect the cable racks where they join
●
Ground the cable racks
●
Connect the shields of the cables to the grounding network as close as possible to the
point of entry into the building or facility.
●
Electrical bus cables installed outside buildings must be included in the lightening
protection and grounding concept of the entire system. Follow the instructions in
Appendix B "Lightning and Surge Voltage Protection for LAN Cables Between Buildings"
of the SIMATIC NET PROFIBUS Networks manual.
●
All SIMATIC NET PROFIBUS cables can be used if they are installed in cable channels
protected against dampness. The safety clearances specified in Appendix C.7 "Cable
categories and clearances" of the SIMATIC NET PROFIBUS Network Manual must then
be adhered to.