Programming
PXL Conventional Fire Alarm Control Panel
43
SET AC FAIL SIGNAL DELAY
- Underwriters Laboratories, Inc.
requires all fire protection systems which communicate to a Central
Station or report as a Remote Station to delay the transmission of AC
Fail Trouble Signals by a predetermined length of time. The system
default is a 6 hour delay which is used for Central Station. For Remote
Station, use the 15 hour delay. The "no delay" option is used for local
fire alarm.
ALARM VERIFICATIONS
- This History selection allows the user to
view any alarm verified zones which went through an alarm verifica-
tion cycle and did not result in an alarm.
ASC AUTOMATIC SYSTEM CONFIGURATION
- This System
mode performs automatically when the System is turned on for the
first time. The PXL first polls all the modules to determine the num-
ber of each type and their addresses. The user is then asked
DO
YOU WANT TO CONFIGURE THE SYSTEM NOW?
Answering
NO
sends
the system into its normal operating mode where all new circuits
operate in default program mode.
Answering
YES
starts the Automatic System Configuration program-
ming of the System. ASC leads the user through the different pro-
gramming functions. The default values of all programmable features
are displayed and the user has the opportunity to change each on
e.
If no selection is made during the ASC routine, the screen will time
out in 20 minutes and start its normal operating mode with all func-
tions operating in default program mode.
When a new module(s) is added to a system that is in operation, the
ASC routine will run on startup. The user will again be asked
DO YOU
WANT TO CONFIGURE THE SYSTEM NOW?
Answering
NO
sends the
system into its normal operating mode. All previous configurations
operate as before; all new modules operate in default mode.
NOTE:
The user
must
view every zone to insure the integrity of
zone operation. At the end of the Automatic System Con-
figuration mode, the system automatically resets and all
program inputs are stored to memory.
CONTROL
- This menu selection allows the user to bypass System
circuits or to test outputs.
DELETE MODULES
- This Program selection allows the user to
confirm that modules have physically been removed from the sys-
tem. When previously installed modules are no longer reporting to
the PXL, the System annunciates a
Module No Response
trouble
condition.