Programming
PXL Conventional Fire Alarm Control Panel
45
MENU
- The menu selection can be accessed at any time, unless
unacknowledged alarms exist in the system. This selection gives the
user access to the Program, Test, Control, and History functions.
PROGRAM
- This menu selection allows the user to program or
reconfigure the System.
To change the custom message, use the INSERT and DELETE
buttons to add or remove character spaces.
Use the LEFT and RIGHT buttons to move the cursor in the
message field. When the cursor is at the selected location in the
field, use the numeric keypad to add numbers and letters.
To select a specific character, press the key to which the charac-
ter is assigned until the desired character displays on the screen.
Note that after all of the characters assigned to a key display, the
sequence of characters repeats if the key is repeatedly pressed.
The keys on the keypad have the following characters assigned
to them:
KEY
ASSIGNED
CHARACTERS
KEY
ASSIGNED
CHARACTERS
1
2
3
4
5
6
A, B, C, 1
D, E, F, 2
G, H, I, 3
J, K, L, 4
M, N, O, 5
P, Q, R, 6
7
8
9
0
*
#
S, T, U, 7
V, W, X, 8
Y, Z, _, 9
0
Future Use
Future Use
When the custom message field is completed, press the DONE
button.
RESPONDING MODULES
- This Program selection allows the user to
review the system modules installed in, and reporting to, the PXL.
SET ALARM VERIFICATION RETARD/RESET TIMER
- The selec-
tion of the Alarm Verification feature results in a delay of the system
alarm signal to the affected circuits. The total allowable delay is 60
seconds. This delay, the Alarm Verification time, is the sum of a built-
in 6 second system delay and the programmed Retard/Reset time.
The Retard/Reset time can be set between 15 and 50 seconds, with
15 seconds being the programmed default. (See the definition of
Zone Types below for a further definition of the Alarm Verification
Time cycle.)
1. To select the proper Retard/Reset time, begin with the Alarm
Verification time required by the system owner or local authority.