Appendix C
PXL Conventional Fire Alarm Control Panel
67
APPENDIX C
Configuring and Programming the PXL
Fire Alarm System for Use in Canada
Module Configuration
The following restrictions on firmware revisions apply:
PCM-1 module must include PXL Revision 3.0 or higher firm-
ware and PCM/PZE Revision 3.0 or higher firmware.
PZE-4B modules must include PCM/PZE Revision 3.0 or higher
firmware.
PPS-10M modules must include PPS Revision 2.0 or higher
firmware.
LED-3/-4 annunciators must include revision 2.0 or higher
firmware.
There are no restrictions on firmware revisions for the following:
PNC-2Z modules
PRM-4 modules
RSA series annunciators
Programming the PXL
Whether programming the System from the Automatic System
Configuration routine or in the Program Mode accessible from the
Main Menu, the Country Code must be set for Canada. This will
cause the first alarm, supervisory, or trouble condition to be continu-
ously reported on the Liquid Crystal Display. Subsequent alarms will
be stored in a queue and can be accessed through the review screen.
The Canada Country Code selection will also cause supervisory
conditions to latch until System reset. All other programming options
follow the instructions in Section 4 (Programming) of this manual.