Troubleshooting
8.5.2
Malfunctions in Reading mode: reading trigger errors
¾
Check whether the "Device Ready" LED lights up.
If the LED does not light, see
CLX in stand-alone configuration
Malfunction
Possible cause
Remedy
1. Trigger mode:
Sensor input
(external sensor).
The CLX cannot be clocked:
– the "Sensor" LED does not light up
– the red scan line does not appear
•
Sensor not connected or connected to
incorrect switching input.
•
If sensor supplied by CLX: sensor not
connected to ground potential.
•
Incorrect reading pulse source para-
meterized in the CLX.
•
Photoelectric switch not aligned with the
reflector (photoelectric proximity switch/
inductive sensor not dampened).
•
Connect sensor to "Sensor" switching
input. Check sensor wiring (see
). Measure output signal on
sensor.
•
Insert jumper between pin 5 and pin 15.
•
In the "CLV-Setup" program: choose the
D
EVICE
C
ONFIGURATION
tab, R
EADING
T
RIGGER
S
OURCE
section: is Sensor input
selected? (active high: reading pulse
starts when power applied)
•
Align sensor.
Check functioning.
2. Trigger mode:
Serial interface
The CLX cannot be clocked:
– the "Sensor" LED does not light up
– the red scan line does not appear
•
Incorrect reading pulse source parame-
terized on the CLX.
•
The CLX is not receiving any command
strings to start the reading interval on the
data interface.
•
In the "CLV-Setup" program: choose the
D
EVICE
C
ONFIGURATION
tab, R
EADING
T
RIGGER
S
OURCE
section: is serial interface
selected?
Click the R
EADING
T
RIGGER
P
ARAMETERS
button, S
ERIAL
I
NTERFACE
section: is trigger
type correct?
•
Check data connection to host. In the
"CLV-Setup" program: choose the H
OST
I
NTERFACE
tab. In D
ATA
F
ORMAT
section: are
the correct interface type (hardware) and
data format selected? I
NTERFACE
P
ROTO
-
COL
section: are the correct start and
stop characters selected?
Use the "CLV-Setup" program to check
the host command strings: choose
A
UXILIARY
I
NTERFACE
tab. Choose
M
ONITOR
H
OST
I
NTERFACE
function. See
Chapter 6.5.6 Monitor Host Interface,
Page 6-22
. Download temporarily to the
CLX.
3. CLX does not respond to an
external signal that ends the reading
pulse (sensor input, serial interface)
Incorrect end of reading pulse para-
meterized on the CLX.
In the "CLV-Setup" program:
choose the D
EVICE
CONFIGURATION
tab, click
the R
EADING
T
RIGGER
P
ARAMETERS
button.
E
ND
OF
R
EADING
I
NTERVAL
section: is Genera-
ted by Trigger Source selected?
Table 8-6: Troubleshooting: reading trigger errors in Reading mode