Terminal module 1 – terminal strip X20
Functional group
Function
+
–
Jumper
1
1
X10.
Switching outputs
2
2
24 VDC/100 mA max; protective diodes must be provided with inductive loads
S01 Measured value valid
2
1
S02 Calibration active
4
3
S03 Malfunction 6
5
J20
18–20
J21
17–19
S04 Service requirement
8
7
S05 Pre-alarm L1
10
9
S06 Alarm L2
12 11
S08 Alarm H2
14 13
J22
16–14
J23
13–15
S07 Pre-alarm H1
16 15
Control inputs
3
3
Max. 24 VDC
SI1 Malfunction, gas supply
18 17
SI2 Calibration block
20 19
SI3 Maintenance block
22 21 J10 + J11
Analog inputs
4
4
Standard: 0 … 10 V; 0 … 20 mA or 4 … 20 mA configurable
AI1 Analog input 1
26 25 J12 + J13
AI2 Analog input 2
28 27 J14 + J15
AI3 Analog input 3
30 29 J16 + J17
AI4 Analog input 4
32 31 J18 + J19
Analog outputs
5
5
Optionally 0 … 20 mA or 4 … 20 mA (
AO1 Measured value
34 33
–
21–22
AO2 Reference value
36 35
–
23–24
Terminal module 1 – terminal strip X10
Functional group
Function
+
–
Jumper
1
1
Explanation
X10.
Analog inputs
2
2
Standard: 0 … 10 V; 0 … 20 mA or 4 … 20
P. 69, §7.1.3mA configurable
Analog input 1
1
2
Analog input 2
3
4
Analog input 3
5
6
Analog input 4
7
8
Control inputs
3
3
Max. 24 VDC
Maintenance block
9
10
without function
11 12
Switching outputs
4
4
24 VDC/100 mA max; protective diodes must be provided with inductive loads
Malfunction 18 17
Feedback malfunction
20 19
J20
18–20
J21
17–19
Alarm
14 13
Feedback alarm
16 15
J22
16–14
J23
13–15
Analog outputs
5
5
Optionally 0 … 20 mA or 4 … 20 mA (
Measured value
21 22
Reference value
23 24
The “Measured value” and “Reference value” analog outputs are potential-free towards the
other electronic components, but not towards one another (joint minus pole).
Summary of Contents for EuroFID
Page 10: ...Contents 10 EuroFID Operating Instructions 8011094 V2 3 SICK AG ...
Page 18: ...18 EuroFID Operating Instructions 8011094 V2 3 SICK AG Important Information ...
Page 80: ...80 EuroFID Operating Instructions 8011094 V2 3 SICK AG Start up ...
Page 88: ...88 EuroFID Operating Instructions 8011094 V2 3 SICK AG Operation General ...
Page 100: ...100 EuroFID Operating Instructions 8011094 V2 3 SICK AG Main Menu Functions ...
Page 144: ...144 EuroFID Operating Instructions 8011094 V2 3 SICK AG Maintenance Sub menu Functions ...
Page 154: ...154 EuroFID Operating Instructions 8011094 V2 3 SICK AG Calibration ...
Page 158: ...158 EuroFID Operating Instructions 8011094 V2 3 SICK AG Shutdown ...
Page 182: ...182 EuroFID Operating Instructions 8011094 V2 3 SICK AG Clearing Malfunctions ...