Installation instructions
Electrical Installation
5.2.11 Information regarding UL
Field wiring power
terminals
Observe the following notes for UL-compliant installation:
• Use 75 °C copper wire only
• Tighten power terminals to 10.6 – 12.4 lb.in (1.2 – 1.4 Nm)
Short circuit
current rating
Suitable for use on a circuit capable of delivering not more than 200,000 rms
symmetrical amperes:
• MOVIGEAR
®
, max. voltage is limited to 500 V.
Branch circuit
protection
Integral solid state short circuit protection does not provide branch circuit protection.
Branch circuit protection must be provided in accordance with the National Electrical
Code and any additional local codes.
For maximum fuse rating see table below.
Motor overload
protection
MOVIGEAR
®
is provided with motor overload protection with a trip current adjusted to
150% of the rated motor current.
Ambient
temperature
MOVIGEAR
®
is suitable for an ambient temperature of 40 °C, max. 60 °C with derated
output current. To determine the output current rating at higher than 40 °C, the output
current should be derated 3.0 % per °C between 40 °C and 60 °C.
Wiring diagrams
For wiring diagrams, please refer to chapter "Electrical installation".
Series
Max. fuse rating
MOVIGEAR
®
40 A / 600 V