Operating Instructions – MOVIGEAR® DAC-B
171
9
Transmitting individual parameters via AS-Interface
Communication with AS-Interface Double Slave GLK31A
Setting the fixed
setpoint n0
Set the fixed setpoint n0 (parameter
8489.0
) to 1000 rpm.
"Write request" service:
The slave replies after the system-related telegram runtime.
"Write response OK" response telegram:
Once the GLK31A double slave has correctly received the data, it immediately sends
the response 0x51 "Write response OK" to the master. Simultaneously, the MOVILINK
®
protocol is sent to the MOVIGEAR
®
inverter.
CTT2 service
MOVILINK
®
protocol
Code
Index Length Addres
sing
Man-
age-
ment
Sub-
index
Index
high
Index
low
MSB
data
Data
Data
LSB
data
0x11
0x02
0x09
0x00
0x32
0x00
0x21
0x29
0x00
0x0F
0x42
0x40
Code 0x11 =
Write request
Index 0x02 =
MOVILINK
®
parameter service
Length 0x09 =
Length of the MOVILINK
®
protocol
Addressing 0x00 =
Addressing the command pcb because this is where the parameter is stored.
Management 0x32 =
Write parameter
Subindex 0x00 =
Subindex of the parameter
Index High 0x21 =
High value of the index
Index Low 0x29 =
Low value of the index
=> Index of parameter = 8489
dec
= 0x2129
hex
The value 0x2129
hex
is written on bytes Index High and Index Low.
Data MSB 0x00
The internal scaling of the MOVIGEAR
®
inverter is 1000 times higher than the
real scaling.
The scaling factor then is 1 000 000
dec
= 0xF4240.
This value is written to the 4 data bytes.
Data 0x0F
Data 0x42
Data LSB 0x40
CTT2 service
Code
0x51
Code 0x51 =
Write response OK