Operating Instructions – MOVIGEAR® DAC-B
187
11
Switch-off responsess
Service
11.3 Switch-off responsess
There are 4 switch-off responses depending on the error; the inverter remains blocked
during the error status:
11.3.1 Immediate disconnection
The unit can no longer decelerate the drive; the output stage goes to high resistance in
the event of a fault. The DynaStop
®
function is activated immediately for units that are
equipped with DynaStop
®
.
11.3.2 Rapid stop
The drive is decelerated with stop ramp t13. When the stop speed is reached, the
DynaStop
®
function is activated for units equipped with DynaStop
®
. Then the output
stage goes to high-resistance.
11.3.3 Emergency stop
The drive is decelerated using emergency stop ramp t14. When the stop speed is
reached, the DynaStop
®
function is activated for units equipped with DynaStop
®
. The
output stage then goes to high-resistance.
11.3.4 Standard stop
The drive is decelerated with the set standard ramp. When the stop speed is reached,
the DynaStop
®
function is activated for units equipped with DynaStop
®
. Then the output
stage goes to high-resistance.
11.4 Resetting error messages
An error message can be acknowledged by:
• Switching power off and on again
• Via controller/PLC: Send "reset command"