D-6 Configuration,
Fast Meter,
and
Fast Operate
Commands
Date Code 20010731
SEL-352-1, -2 Instruction Manual
2C
Operate code, set remote bit RB13
4C
Operate code, pulse remote bit RB13
0D
Operate code, clear remote bit RB14
2D
Operate code, set remote bit RB14
4D
Operate code, pulse remote bit RB14
0E
Operate code, clear remote bit RB15
2E
Operate code, set remote bit RB15
4E
Operate code, pulse remote bit RB15
0F
Operate code, clear remote bit RB16
2F
Operate code, set remote bit RB16
4F
Operate code, pulse remote bit RB16
00 Reserved
1-byte
Checksum of all preceding bytes
A5E0
Fast Operate
Remote Bit Control
Fast Operate
Remote Bit Control is suspended during relay setting changes, a setting group
change, power-up, or if the relay is disabled. The external device sends the following message to
perform a remote bit operation:
Data Description
A5E0 Command
06
Message length (hex)
1-byte Operate
code:
00 - 0F clear remote bit RB1 - RB16
20 - 2F set remote bit RB1 - RB16
40 - 4F pulse (1/8 - cycle) remote bit RB1 - RB16
1-byte
Operate validation: 4
¼
Operate code + 1
1-byte
Checksum of all preceding bytes
The relay performs the specified remote bit operation if the following conditions are true:
The Operate code is a valid code
The Operate validation = 4
¼
Operate code + 1
The message checksum is valid
The FAST_OP port setting is set to Y
The relay is enabled
Remote bit set and clear operations are latched by the relay. Remote bit pulse operations assert
the remote bit for one processing interval (1/8 cycle).
Summary of Contents for SEL-352-1
Page 8: ......
Page 10: ......
Page 12: ......
Page 30: ......
Page 68: ......
Page 186: ......
Page 292: ......
Page 302: ......
Page 368: ......
Page 370: ......
Page 374: ......
Page 380: ......
Page 382: ......
Page 384: ......
Page 386: ......
Page 396: ......
Page 404: ......
Page 422: ......
Page 442: ......