11-28
Testing and Troubleshooting
Date Code 20010731
SEL-352-1, -2 Instruction Manual
Setting
Elements
59L, VNpu,
TRIPA, CLOSE,
MCLOSE, 52AA
KTRK, X59LA, Y59LA, MCLOSE, CLOSE,
TRIPA, 52AA
2. Apply 67 V to VAX and VAY inputs, which should be above the 59L setting.
Verify that these elements are asserted by typing
TAR X59LA<ENTER>
and
TAR Y59LA<ENTER>
.
3. Apply dc control voltage to the input assigned to 52AA.
4. Verify that the SEL-352 Relay is tracking the voltage by typing
TAR KTRK
<ENTER>.
KTRK should be a logical one after the VNpu time delay. The
default setting is VNpu = 10 minutes.
5. Trigger an event report by typing
TRI <ENTER>.
6. View the event report by typing
EVE <ENTER>.
Use
<CTRL>X
to cancel the
scrolling when the voltage nulling factors appear.
7. Verify that A-phase voltage nulling magnitude is 1 and the angle is 0.
8. Change the magnitude of the X or Y voltage to 70 V. Repeat Steps 4, 5, and 6.
The nulling magnitude should now be approximately 1.04 or 0.96 depending on
which value was changed.
9. Change the angle of the X or Y voltage by 2
. Repeat Steps 4, 5, and 6. The
nulling angle should now be 2
.
10. Repeat Steps 2 through 9 for B and C phases.
11. Optional. Change the magnitudes and angles of the voltages and verify the
voltage nulling tracking. The relay will not track (KTRK = 0) if either voltage is
below the 59L setting or TRIPA, CLOSE, or MCLOSE are asserted. If any of
these conditions disable the tracking, the K value is held at its most recent
calculation. If KMAG is exceeded or KANG is exceeded, the K value is held at
the maximum values, but the relay is still tracking (KTRK = 1).
12. Using the
SET
command, program an output contact to close when the KTRK bit
is asserted.
13. Connect a timer to start timing when dc control voltage is applied to the input
assigned to 52AA and stop when the output contact programmed in Step 12
closes.
14. Apply 67 V to the X and Y voltage inputs.
15. Apply dc control voltage to the input assigned to 52AA. This should start the
timer. KTRK asserts VNpu minutes after the input is asserted. Verify your timer
value with the VNpu setting.
Summary of Contents for SEL-352-1
Page 8: ......
Page 10: ......
Page 12: ......
Page 30: ......
Page 68: ......
Page 186: ......
Page 292: ......
Page 302: ......
Page 368: ......
Page 370: ......
Page 374: ......
Page 380: ......
Page 382: ......
Page 384: ......
Page 386: ......
Page 396: ......
Page 404: ......
Page 422: ......
Page 442: ......