S
ETTINGS
W
ORKSHEET
Page
12 of 28
FOR THE
SEL-352-1, -2 R
ELAY
Date ________
Date Code 20010731
Dielectric Monitor Logic Settings
Description Range
Loss of Dielectric Logic
OFF, ON, CUSTOM
DELOG =
If DELOG = ON
62L2 Leak Timer Pickup Time
0–16383 cycles in 1/4-cycle steps
L2pu =
If DELOG = Custom
62L2 Leak Timer Pickup Time
0–16383 cycles in 1/4-cycle steps
L2pu
=
Loss of Dielectric Timer 62LT1, 62LT2, and 62LT3
LT1 =
LT2 =
LT3 =
Loss of Dielectric Pending Failure
LODPF =
Loss of Dielectric Breaker Failure
LODBF =
Controlled Close Logic Settings
4
Description Range
Live Line/Bus Voltage
10.0–120.0 V in 0.1-V steps
59L =
Dead Line/Bus Under Voltage
1.0–120.0 V in 0.1-V steps
27D =
Controlled Close Logic
OFF, 1, 2, CUSTOM
CLSLOG =
If CLSLOG = 1
62CLS Timer Dropout Time
0–16383 cycles in 1/4-cycle steps
CLSdo =
62RCA Timer Pickup Time
0–16383 cycles in 1/4-cycle steps
RCApu =
62RCB Timer Pickup Time
0–16383 cycles in 1/4-cycle steps
RCBpu =
62RCC Timer Pickup Time
0–16383 cycles in 1/4-cycle steps
RCCpu =
If CLSLOG = 2
62CLS Timer Dropout Time
0–16383 cycles in 1/4-cycle steps
CLSdo =
Maximum Slip Freq. for Control
Close
0.005–0.500 Hz in 0.001-Hz steps
25SC =
Maximum Control Close Angle
32
•
25SC to 90
(min =1) in 0.1
steps
25AC =
Maximum Slip Freq. for Manual
Close
0.005–0.500 Hz in 0.001-Hz steps
25SM =
Maximum Manual Close Angle
32
•
25SM to 90
(min =1) in 0.1
steps
25AM =
Synchronizing Phase
A, B, C
SYNCP =
4
Volts are set in secondary quantities.
Summary of Contents for SEL-352-1
Page 8: ......
Page 10: ......
Page 12: ......
Page 30: ......
Page 68: ......
Page 186: ......
Page 292: ......
Page 302: ......
Page 368: ......
Page 370: ......
Page 374: ......
Page 380: ......
Page 382: ......
Page 384: ......
Page 386: ......
Page 396: ......
Page 404: ......
Page 422: ......
Page 442: ......