B-4
Firmware Upgrade Instructions
Date Code 20010731
SEL-352-1, -2 Instruction Manual
If this occurs, press
<ENTER>
to see if the level 0 prompt “ = ” appears on your
terminal screen. If it does, enter Access Level 2 by issuing the
ACC
and
2AC
commands and proceed to self-test failure:
IO_BRD
, Step 13a.
If the relay does not display the level 0 “ = ” prompt, the Relay baud rate has reverted to
the factory default of 2400 baud. Go to Self-test failure:
CR_RAM, EEPROM,
and
IO_BRD
, Step 13d.
Self-test failure:
IO_BRD
a. Issue the Initialize (
INI)
command to reinitialize the I/O Board(s). If this
command is not available, go to Step 13e.
b. Answer
Y
<ENTER>
to the question: “Are the new I/O board(s) correct
(Y/N)” After about ten seconds, the EN LED will illuminate. The original
relay settings have been retained but should be checked for accuracy.
c. Enter Access Level 2 by issuing the
ACC
and
2AC
commands. Go to
Step 14.
Self-test failure:
CR_RAM, EEPROM,
and
IO_BRD
d. Set your communications software settings to 2400 baud, 8 data bits, 1 stop
bit. Now enter Access Level 2 by issuing the
ACC
and
2AC
commands, (see
PAS (Passwords)
in
Section 8: Serial Port Communications and Commands
for factory default passwords).
e. Issue the Restore Settings (
R_S
) command to restore the factory default
settings in the relay. For a 1 Amp relay, type
R_S 1
. This takes about two
minutes, after which time the EN LED will illuminate.
Note:
If the relay asks for a part number to be entered, use the number from
the label on the firmware diskette, or from the new part number sticker (if
supplied).
f. Enter Access Level 2 by issuing the
ACC
and
2AC
commands, (see
PAS
(Passwords)
in
Section 8: Serial Port Communications and Commands
for
factory default passwords).
g. Restore the original settings as necessary with each of the following
commands:
SET 1
,
SET 2
,
SET 3
,
SET 4
,
SET 5
,
SET 6
,
SET G
,
SET P 1
,
SET P 2
,
SET P 3
,
SET P 4
,
SET R
.
h. Use
the
PAS
command to set the original relay passwords you saved earlier in
Step 3.
For
example,
PAS 1:Ot3579 <ENTER>
sets the level 1 password to Ot3579.
Use a similar format for
PAS B
and
PAS 2
. The
PAS
command is
case-sensitive, so the lower- and upper-case letters are treated differently.
If any FAIL codes show on the Relay LCD, see
Section 11: Testing and
Troubleshooting.
14. Verify the calibration settings by issuing the
SHO C
command. If the settings do not
match the settings recorded in Step 3, reissue the settings with the
SET C
command.
Summary of Contents for SEL-352-1
Page 8: ......
Page 10: ......
Page 12: ......
Page 30: ......
Page 68: ......
Page 186: ......
Page 292: ......
Page 302: ......
Page 368: ......
Page 370: ......
Page 374: ......
Page 380: ......
Page 382: ......
Page 384: ......
Page 386: ......
Page 396: ......
Page 404: ......
Page 422: ......
Page 442: ......