11-26
Testing and Troubleshooting
Date Code 20010731
SEL-352-1, -2 Instruction Manual
7. Apply A-phase current equal to the magnitude Ia calculated above. The external
timer should start upon application of A-phase current.
8. Shortly after you apply phase current, the programmable output contact set in
Step 1 should close, indicating CTF bit assertion. This action should stop the
external timer. Record the timer reading. It should be close to the TTT value
calculated above plus the OPpu timer setting.
9. Shut off phase current.
10. In Step 6, accumulation of breaker resistor energy equal to the 26CP thermal
pending failure value can cause the relay to generate an event report. You can set
the 26CPA bit in a programmable output contact mask and perform Steps 4, 5, 6,
7, 8, and 9 for the close resistor thermal pending failure logic.
11. You may wish to test this logic for various values of input voltage, current, and
power. Use the
HEAT
command to display the per-unit energy content of the
breaker resistor thermal models. Use the
HEA R
command to reset the thermal
models before each timing test.
12. Repeat Steps 4–11 for B- and C-phases.
13. For each test, the relay generated a sequential events record for the elements
programmed in Step 1. View the SER using the
SER
command. These time
stamps will also verify the OPpu timer. The OPpu time is the time between the
assertion of 37OPA and the assertion of OPAD.
C
IRCUIT
B
REAKER
T
RIP
R
ESISTOR
T
HERMAL
F
AILURE
L
OGIC
T
EST
Purpose: Verify operation of the breaker trip resistor thermal failure logic (Reference:
Figure 3.19).
Method: 1. Using
the
SET
command, set an output to close when the TTF element asserts,
and set the SER to trigger for the elements listed below. Verify the settings with
the
SHO
command, and the
SHO G
command for 52AA and TRIPA. Note that
THLOG must be set to ON.
Setting
Elements
THLOG, 50MN,
26TF, 37OP, 87TH,
OPpu, 52AA, TRIPA
(47Q not used)
TTF, 50MNA, 37OPA, 87THA, OPAD,
52AA, TRIPA
2. Use
the
HEA R
command to reset the thermal models before each timing test.
3. Connect an external timer and set it to start when you apply A-phase current and
stop when the programmable output you set in Step 1 asserts.
4. Assert the TRIPA input by applying dc control voltage to the input terminals.
5. Apply voltage higher than the 87TH setting to the A-phase voltage input.
Summary of Contents for SEL-352-1
Page 8: ......
Page 10: ......
Page 12: ......
Page 30: ......
Page 68: ......
Page 186: ......
Page 292: ......
Page 302: ......
Page 368: ......
Page 370: ......
Page 374: ......
Page 380: ......
Page 382: ......
Page 384: ......
Page 386: ......
Page 396: ......
Page 404: ......
Page 422: ......
Page 442: ......