Date Code 20010731
Command Summary
1
SEL-352-1, -2 Instruction Manual
SEL-352-1, -2 R
ELAY
C
OMMAND
S
UMMARY
ASCII
Command
Command Description
Minimum
Access
Level
Front-
Panel
Equivalent
2AC
ACC
BAC
Enter Access Level 2, 1, or B. Install main board password
jumper JMP6A to disable password protection.
1, B
0
1
Relay
prompts if
necessary
BRE
BRE C
BRE R
BRE S
BRE W
Display detailed breaker pole operations, summary, and alarms.
Clear breaker pole operations, operation summary, and alarms.
Clear breaker pole operations, operation summary, and alarms
(SEL-352-2 Relay only).
Display only breaker operation summary and alarms.
Preload breaker wear data (SEL-352-2 Relay only).
1
2
2
1
B
EVENTS
CAL
Enter the calibration access level.
2
CEVE
Display compressed version of EVE for SEL-5601 software.
1
CLO
Assert the CCMD bit for 30 cycles. JMP6B must be in place.
B
CNTRL
CON n
Control Remote Bit RBn.
2
COP m n
Copy settings from group m (1, 2, or 3) to group n (1, 2, or 3).
2
DAT
DAT d1
Display relay date according to the format setting DATE_F.
Set relay date to d1. If the date format setting DATE_F = MDY,
d1 is m/d/y. If DATE_F = YMD, d1 is y/m/d.
1
OTHER
EVE
n
A
Ss
Lc
Display an event report with VX and I channels.
n specifies event number according to the HIS command.
A specifies the alternate report showing VY (not VX and I).
Ss specifies the samples per cycle (s = 4, 8, 16, 64).
Lc specifies the length in cycles (c = 1 to LER setting).
Unspecified options are n = 1, no A, s = 4, and c = LER.
1
GRO
GRO n
Display the active setting group number and group variable.
Change the group variable to n (n = 1, 2, or 3).
1
2
GROUP
GROUP
HEA k
HEA C
HEA R
Display the energy in the trip and close resistors k times.
Reset the thermal model to zero.
Reset the thermal model to zero.
1
2
2
HIS n
HIS C
Show the summaries of the n latest events.
Clear all of the summaries and corresponding events.
1
2
EVENTS
INI
Initialize and display the inputs and outputs per I/O board.
1
IRI
Attempt IRIG-B time-code input synchronization. The relay
attempts synchronization automatically every minute.
1
MET k
Display metering data k times.
1
METER
OPE
Assert the TCMD bit for 30 cycles. JMP6B must be in place.
B
CNTRL
Summary of Contents for SEL-352-1
Page 8: ......
Page 10: ......
Page 12: ......
Page 30: ......
Page 68: ......
Page 186: ......
Page 292: ......
Page 302: ......
Page 368: ......
Page 370: ......
Page 374: ......
Page 380: ......
Page 382: ......
Page 384: ......
Page 386: ......
Page 396: ......
Page 404: ......
Page 422: ......
Page 442: ......