3-50
Breaker Logic
Date Code 20010731
SEL-352-1, -2 Instruction Manual
Slow Close
SC asserts if the 52AA bit does not indicate a closed breaker Tclose time following the
respective phase close input assertion. The SlowC1 timer resets when 52AA asserts.
Figure 3.37: Slow Close
Potential Transformers Disagree
The PTD bit asserts if the voltage nulling constant K (see
Voltage Nulling
) exceeds the Kmag or
Kang setting.
Figure 3.38: Potential Transformers Disagree
To disable any of the above breaker monitors, remove the element from the BALRM setting list.