Date Code 20010731
Testing and Troubleshooting
11-41
SEL-352-1, -2 Instruction Manual
20. For each test, the relay generated a sequential events record for the elements
programmed in Step 1. View the SER using the
SER
command. Verify M1 (60
cycles) from the assertion of 86RS to the deassertion of 86RS. Verify M2pu from
the assertion of 86BFT to the assertion of MDT. Verify M3pu from the assertion
of MDT to the deassertion of 86BFT. Verify M4 (300 cycles) from the
deassertion of 86BFT to the assertion of 86RS.
S
ERIAL
P
ORTS
T
EST
Purpose: Verify operation of each serial PORT.
Method: Step 3 of the initial checkout procedure describes serial port connections for Ports 2,
3, and 4. Following that same procedure, verify communications on each serial port.
Port 1, the EIA-485 serial port, requires an EIA-232 to EIA-485 converter and cable to
connect to a computer.
IRIG-B T
IME
-C
ODE
I
NPUT
T
EST
Purpose: Verify operation of the IRIG-B clock input for Serial Port 2 and the connector of
Serial Port 1.
Method: 1. Connect a source of demodulated IRIG-B time code to the relay Serial Port 2
(Pins 4 (+) and 6 (–)) in series with a resistor to monitor the current. Adjust the
source to obtain an “ON” current of about 10 mA.
2. Execute
the
IRIG
command. Make sure the relay clock displays the correct date
and time.
3. Optional. Connect the demodulated IRIG-B time code to the relay as in Step 1, but
through the Serial Port 1 connector (Pins 7(+) and 8 (–)).
P
OWER
S
UPPLY
V
OLTAGES
T
EST
Purpose: Verify that +5 Vdc is present on Port 2 and 3. This voltage is sometimes required by
external devices that include a dc-powered modem.
Method: 1. Execute
the
STATUS
command, and inspect the voltage readings for the power
supply.
2. Verify that JMP1 is installed for Serial Port 3 and JMP2 is installed for Serial Port
2. Refer to
Section 2: Installation
for further information about the jumpers.
3. Use a voltmeter to read the +5 V output. Pin 1 of each port should have +5 Vdc
on it when the jumpers mentioned above are installed.
4. Compare the +5 V readings from the status report and voltmeter. The voltage
difference should be less than 50 mV, and both readings should be within ±0.15 V
of 5 V.
Summary of Contents for SEL-352-1
Page 8: ......
Page 10: ......
Page 12: ......
Page 30: ......
Page 68: ......
Page 186: ......
Page 292: ......
Page 302: ......
Page 368: ......
Page 370: ......
Page 374: ......
Page 380: ......
Page 382: ......
Page 384: ......
Page 386: ......
Page 396: ......
Page 404: ......
Page 422: ......
Page 442: ......