Date Code 20010731
Setting the Relay
7-25
SEL-352-1, -2 Instruction Manual
Controlled Closing Scheme 2 (Point-on-Wave Closing)
The default SEL
OGIC
control equation settings for the controlled closing logic Scheme 2 follow:
RCLS =TRIPA + TRIPB + TRIPC
RCA =NA
RCB =NA
RCC =NA
CCT =CLOSE
MCT =MCLOSE
SYNCT =CLOSE
SCT =25M*MCTD + !X59L3*!Y59L3*MCTD + 25C*SYNCTD
ZCNA =(CCTD + MCTD)*!XPTA*!XNTA*!YPTA*!YNTA*(X59L3*!Y59L3 + !X59L3*Y59L3)
ZCNB =(CCTD + MCTD)*!XPTB*!XNTB*!YPTB*!YNTB*(X59L3*!Y59L3 + !X59L3*Y59L3)
ZCNC =(CCTD + MCTD)*!XPTC*!XNTC*!YPTC*!YNTC*(X59L3*!Y59L3 + !X59L3*Y59L3)
ZCPA =NA
ZCPB =NA
ZCPC =NA
PCNA =(CCTD + MCTD)*(XNTA + YNTA)*(X59L3*!Y59L3 + !X59L3*Y59L3)
PCNB =(CCTD + MCTD)*(XNTB + YNTB)*(X59L3*!Y59L3 + !X59L3*Y59L3)
PCNC =(CCTD + MCTD)*(XNTC + YNTC)*(X59L3*!Y59L3 + !X59L3*Y59L3)
PCPA =(CCTD + MCTD)*(XPTA + YPTA)*(X59L3*!Y59L3 + !X59L3*Y59L3)
PCPB =(CCTD + MCTD)*(XPTB + YPTB)*(X59L3*!Y59L3 + !X59L3*Y59L3)
PCPC =(CCTD + MCTD)*(XPTC + YPTC)*(X59L3*!Y59L3 + !X59L3*Y59L3)
SYNCEN =!52AA*!52AB*!52AC
CCA =CTAD + SCTD
CCB =CTBD + SCTD
CCC =CTCD + SCTD
Retripping Scheme 1
The default SEL
OGIC
control equation settings for the retripping logic Scheme 1 follow:
LRTAS =NA
LRTAR =NA
LRTBS =NA
LRTBR =NA
LRTCS =NA
LRTCR =NA
RT1 =NA
RT2 =NA
RT3 =NA
RTA =TRIPA
RTB =TRIPB
RTC =TRIPC
Summary of Contents for SEL-352-1
Page 8: ......
Page 10: ......
Page 12: ......
Page 30: ......
Page 68: ......
Page 186: ......
Page 292: ......
Page 302: ......
Page 368: ......
Page 370: ......
Page 374: ......
Page 380: ......
Page 382: ......
Page 384: ......
Page 386: ......
Page 396: ......
Page 404: ......
Page 422: ......
Page 442: ......