Installation manual
PSC1-C-10 Installation manual V2.6
Page 45 of 173
Version: 57E
4.2.1.4
Connection examples, digital sensors/safety switch
Attention! Identifiers for "Xxy" terminal blocks (e.g. X14) are not printed on the terminal blocks. They
are used in Section 5.6 Terminal assignment to find the individual terminals more quickly, e.g. "I00".
4.2.1.4.1
Single-channel sensor, without cross-circuit testing
I00
I01
I02
I03
T0
T1
L+
L-
X14
X12
.
.
.
Single-channel sensor, without cross-circuit testing
The single-channel sensor is connected to the PSC1 without test pulses, and without cross-circuit
testing. This design is not recommended for safety applications. Max. PL b according to EN ISO 13849-1
can be achieved.
4.2.1.4.2
Single-channel sensor with cross-circuit testing
L+
L-
T1
T0
I00
I01
I02
I03
T0
T1
X14
X12
.
.
.
Single-channel sensor with test pulses