![schmersal PSC1-C-10 Series Installation Manual Download Page 16](http://html1.mh-extra.com/html/schmersal/psc1-c-10-series/psc1-c-10-series_installation-manual_1213105016.webp)
Installation manual
PSC1-C-10 Installation manual V2.6
Page 16 of 173
Version: 57E
3.2
Device characteristic data
3.2.1
Basic modules
3.2.1.1
PSC1-C-10 (-FBx
(1)
/-MC)
Type designation
Device features
Version of the module with following peripherals:
14
digital inputs
2
pulse outputs
2
relay outputs (1-channel)
2/4
pn or pp switching outputs
2
signal outputs
1
diagnostics and configuration interface
1
function button
1
7-segment display
1
status LED
14
status LEDs for inputs
2
status LEDs for signal outputs
2
status LEDs for relay outputs
4
status LEDs for outputs
1
optional: Communication interface incl.
Memory card slot (-FBx
(1)
)
1
optional: Memory card slot (-MC)
Properties of the module:
•
Can be expanded to:
o
Max. 42 safe digital inputs,
o
Max. 12 safe digital outputs,
o
Max. 20 safe digital I/O,
o
Max. 5 safe relay outputs (2-channel),
o
Max. 6 signal outputs
•
Logic processing up to PL e according to EN ISO 13849-1 or SIL 3 according to EN 61508
•
Freely programmable small controller for up to 800 IL instructions
•
Function plan-orientated programming
•
Pulse outputs for cross-circuit detection on digital input signals
•
Safety function, external contact monitoring on switchgear connected
•
Monitored relay outputs for safety-related functions
•
External contact monitoring on switchgear connected (EMU)
•
Monitored relay outputs for safety-related functions
•
Switchable safe outputs pn, pp switching for safety-related functions
•
Parameter administration for expansion modules in the basic device
•
Comprehensive diagnostic functions integrated in the firmware
•
Coded status indication via 7-segment display and status LEDs on front
•
Multi-function button (Quit, Start, Reset) can be operated from the front