Determination of the total response time
T
TOTAL
= T
IN
+ T
PLC
+ T
OUT
Example 1:
Input on expansion module, activation of SLS and processing in PLC, output on basic module
T
TOTAL
= T
IN_31
+ T
PLC
+ T
OUT_Base
= 18 ms + 8 ms + 0 ms = 26 ms;
Example 2:
Input on basic module, activation of SLS and processing in PLC, output on expansion module
T
TOTAL
= T
IN_Base
+ T
PLC
+ T
OUT_31
= 10 ms + 8 ms + 8 ms = 26 ms;
Example 3:
Input on expansion module, activation of SLS and processing in PLC, output on expansion module
TTOTAL = TPLC + TOUT_31 = 18 ms + 8 ms + 8 ms = 34 ms;