Installation manual
PSC1-C-10 Installation manual V2.6
Page 144 of 173
Version: 57E
Typ
e
Switch symbol
Truth table
Function
11
eTwoHand_2o
N
C1
N
O
1
N
C2
N
O
2
A
0
1
0
1
0
1
0
0
1
0
1
0
1
0
0
0
1
0
1
1
Two-hand control
MEZ
Monitoring for NO1*NO2 = inactive
and NC1*NC2 = time
monitoring of this state. I.e. if there
is a signal change on an NO from 1-
>0 or NC from 0->1 then the other
signals (i.e. further NO=0 or NC=1)
must follow within 0.5 s. If not the
output remains = 0.
No malfunction evaluation! No
time monitoring on change to
inactive state.
Öffner 2
Ausgang
Öffner 1
max. 0,5 s
12
eTwoHand_2s
NO
1
N
O2
A
1
0
0
0
1
0
0
0
0
1
1
1
Two-hand control
MEZ
Monitoring for NO1*NO2 = inactive
+ time monitoring of this state. I.e.
if there is a signal change on an NO
from 1->0 then the other signal (i.e.
further NO=0) must follow within
0.5 s. If not the output remains = 0.
No malfunction evaluation! No
time monitoring on change to
inactive state.
Ausgang
Schließer 1
max. 0,5 s
Schließer 2