Installation manual
PSC1-C-10 Installation manual V2.6
Page 124 of 173
Version: 57E
6.4
Response times when using the PSC1-E-3x
The basis for the calculation of response times is the cycle time of the PSC1. system. During operation
this is
T_cycle = 8 ms
. The response times stated correspond to the related maximum propagation
time within the PSC1 module for the specific application. Depending on the application, further
application-dependent response times for the sensors and actuators used must be included in the
calculation to obtain the total propagation time.
Function
Identifier
Response
time [ms]
Explanation
Worst-case delay, input in the basic
module to the PAE
T
IN_BASE
10
E.g. activation of a monitoring function by an input
signal in the
basic module
Worst-case delay, input PSC1-E-31 to
the PAE in basic module
T
IN_31
18
E.g. activation of a monitoring function by an input
signal in the expansion module PSC1-E-31
Processing time PAE to PAA in basic
module
T
PLC
8
Shutdown by a monitoring function or by an
input in the PAE
Activation / deactivation of digital
output in basic module from PAA
T
OUT_BASE
-
Activation or deactivation of an output in the
basic module after change in the PAA
Activation / deactivation of digital
output in expansion module via PAA
on basic module
T
OUT_31
8
Activation or deactivation of an output in the
expansion module PSC1-E-31 after change in
the PAA in the basic module