Installation manual
PSC1-C-10 Installation manual V2.6
Page 138 of 173
Version: 57E
10
Technical data
10.1
Ambient conditions
Degree of protection
IP 20
Ambient temperature
0 °C* ... 50 °C
Storage temperature
-
25°C … 70°C
Climatic class
3k3 according to DIN 60 721
Minimum, maximum relative
humidity (non-condensing)
5-85%
Overvoltage category
III
Degree of pollution (IEC/EN
60664-1)
2
Max. Installation height
2000m
10.2
Safety-related characteristic data
Max. achievable safety class
•
SIL 3 as per EN61508
•
Category 4 as per EN945-1
•
Performance Level e as per EN ISO 13849-1
System structure
2-channel with diagnostics (1002) according to EN
61508
Architecture category 4 according to EN ISO 13849
Design of the operating mode
"High demand" as per EN 61508
Probability of a dangerous failure per hour
(PFH value)
Specific values as per tables "Safety-related
characteristic data"
PSC1-C-10-x
see section 3.2.1
PSC1-E-3x
see section 3.2.2
Proof test interval (IEC 61508)
20 years, after that the module must be replaced