108
Installation manual of system “bp408” - Commissioning
The drive with the maximum speed must be decelerated at these deceleration
points and may not overrun the levelling position of the end stop.
The deceleration is initiated when the switches of the direction of travel
correspondingly open.
The delay switch S81 opens during the upward drive and always starts the slow
speed (V0) before the upper end stop.
The delay switch S82 opens during the downward drive and always starts the slow
speed (V0) before the lower end stop.
Setting in the setup menu:
> FUNCTIONS
> COPYING TOOL
> PRE-LIMIT SWITCH
(S81/82
) ON
8.12
First drive in the normal operation
WARNING!
All points must be checked for your own safety. Also follow the safety information
in chapter 2.
Have you followed all points of the previous checklists (see chapter 8.4 and 8.5)?
Yes □
No current faults are displayed on the LCD display of the bp408 and of the drive?
Yes □
The return control and the inspection control are functional, as described in chapter 8.7
and 8.8.
Yes □
The emergency limit switches are installed, configured and tested for functioning.
Yes □
The safety switches are installed, configured and tested for functioning.
Yes □
Figure 68:
Impulse diagram with magnetic switches and AWG-05
Summary of Contents for bp408
Page 2: ......
Page 24: ...24 Installation manual of system bp408 Safety instructions...
Page 52: ...52 Installation manual of system bp408 The control system bp408...
Page 58: ...58 Installation manual of system bp408 Installation and assembly...
Page 80: ...80 Installation manual of system bp408 Electrical connection...
Page 118: ...Installation manual of system bp408 Appendix 118 Appendix A Menu navigation bp408...
Page 119: ...119 Installation manual of system bp408 Appendix B Update of the firmware via USB stick...