Installation manual of system “bp408” - Commissioning
111
8.16
Setting up the modem
If an analogue modem, which must correspond to the V 250 standard, is used for
remote diagnostics, the parameters for the communication can be entered after
the wiring has been completed. These include, in particular, the interface used, the
DFÜ300 protocol, the telephone numbers to be called in case of faults and
emergencies. Furthermore, you should set when a callback to the control centre
should be made, for every fault, only in case of lock, or never.
8.17
Setting up a networkconnection
If the remote diagnosis is carried out via a network connection, the following
parameters must be entered:
IP address: e.g. 192.168.0.119
Subnet mask: e.g. 255.255.255.0
Gateway: e.g. 192.168.0.2
Port: e.g. 8000 (default setting)
NOTE!
The IP address, subnet mask and the gateway are provided by the administrators
of the network. The port 8000 must be available on the network. The protocol used
is TCP/IP. Further information about the remote diagnosis can be found in the
current WinMOS
®
300manual.
8.18
Completion of commissioning
After completion of the commissioning, it is advisable to store the current
parameterisation of the system in the documents. To do this, read the parameters
with WinMOS
®
300 from the system and attach the printout to the documents. If
WinMOS
®
300 is not available for you, note down the settings in the attached
printout of the setup and service menu.
The faults stored in the stack memory and the fault list during commissioning as
well as the entries in the maintenance stack can be deleted.
If access by third parties (such as janitors) is possible, you should protect access
to the menus by assigning a setup and service code.
Summary of Contents for bp408
Page 2: ......
Page 24: ...24 Installation manual of system bp408 Safety instructions...
Page 52: ...52 Installation manual of system bp408 The control system bp408...
Page 58: ...58 Installation manual of system bp408 Installation and assembly...
Page 80: ...80 Installation manual of system bp408 Electrical connection...
Page 118: ...Installation manual of system bp408 Appendix 118 Appendix A Menu navigation bp408...
Page 119: ...119 Installation manual of system bp408 Appendix B Update of the firmware via USB stick...