Saia-Burgess Controls AG
Manual I/O-modules for PCD1 │ PCD2 series │ Document 27-600 – Release ENG09 │ 2019-05-01
5-109
I/O modules PCD1|PCD2
PCD2.H100
5
5.16.1
PCD2.H100, counting module up to 20 kHz
Application
Simple counting module, comprising two inputs “A” and “B” plus one direct
control output marked “CCO”; allows counting of the number of revolutions or
the calculation of distances (pulses) and the measurement by counting of pulses
within a logical AND gate (second input).
Typical areas of application:
● Counting revolutions or distances (impulses)
● Presetting a count value and switching off output CCO when Counter = 0
● Measurement by counting: measuring signals counted only when particular
conditions are met, e.g. photoelectric barrier covered
● Counting with recognition of count direction for incremental shaft encoders
providing simple motion control
Technical data
Number of systems:
1
Counting range:
0 …
65,535 (16 bit, can be ext. with CPU counters)
Counting frequency:
max. 20 kHz (at pulse/pause ratio 50 %)
Data protection:
All data in this module are volatile
(non-volatile Saia PCD
®
registers are available).
Digital inputs
“IN-A” and “IN-B” signal voltages: nominal voltage: 24 VDC
“low” range:
-30 … +5 V
“high” range:
+15 … 30 V
for source operation
Input current:
typically 7.5 mA
Input filer:
25 kHz
Process output
Counter controlled output CCO:
counter output (switches when count is 0 or 65,535)
Current range:
5 … 500 mA (max. current leakage 1 mA)
(min. load resistance
48 Ω in
voltage range 5 … 24 V
).
Voltage range:
5 … 32 V smoothed,
residual ripple max. 10 %
Circuit type:
Electrically coupled, not short circuit protected,
positive switching
Voltage drop:
typically 2V at 500 mA
Output delay:
< 10 µs
(longer for inductive load due to
protective diode).
Power supply
External supply
5 … 32 VDC (
for supply of CCO output only)
Internal current consumption:
(from +5 V bus)
max. 90 mA
Internal current consumption:
(from V+ bus)
0 mA
External current consumption:
CCO output load current
Operational conditions
Ambient temperature
operation: 0 … +55 °C without forced ventilation,
storage:
-20 … +85 °C
Noise immunity:
EC mark according to EN 61 000-6-3 / EN 61 000-6-2
Programming:
Based on Saia PCD
®
user program and pre-pro-
grammed function blocks (FB).
Count modes:
Selectable with jumper
Terminals:
Pluggable 10-pole screw terminal block
(4 405 4847 0), for wires up to 1.5 mm²