Saia-Burgess Controls AG
Manual I/O-modules for PCD1 │ PCD2 series │ Document 27-600 – Release ENG09 │ 2019-05-01
6-8
I/O modules PCD3
Introduction to I/O modules
6
6.1.2
Current consumption of the modules
Type
PCD3…
Internal current
consumption
I from +5 V [mA]
Internal current
consumption
I from V+ [mA]
External current
consumption
I from 24 V
DC
E11x
1…24
--
max. 48 mA
E16x
1…10
--
max. 64 mA
E500
1
--
--
E61x
1…24
--
max. 40/30 mA
A200
1…15
--
max. 32 mA
A210
1…15
max. 32 mA
A220
1…20
--
max. 48 mA
A251
1…25
--
max. 64 mA
A300
1…20
--
Load current
A400
1…25
--
Load current
A410
1…24
--
Load current
A46x
max. 10
--
Load current
A810
40
--
--
A860
18
--
--
B100
1…25
--
Load current
B100
120
--
Load current
W200/210
8
5
--
W220
8
16
--
W300/310
8
5
--
W340/360
8
20
--
W350
8
30
--
W380
25
25
--
W3x5
60
--
--
W4x0
1
30
100 mA (W410)
W600
max. 4
20
--
W610
max. 110
--
max. 100 mA
W6x5
110/55 (W615)
90 (W615)
max. 90 mA (W615)
W500
max. 200
--
--
W525
40
0
--
W7x0
W745
200
--
W800
45
35
H100
90
--
CCO output, load current
H110
90
--
Load current
H150
25
--
Load current
H210 ¹)
85
--
Load current
H31x ¹),
2
)
140
--
max. 15 mA
¹) These I/O modules cannot currently be used with the PCD3 RIO head station
2
) for H311: up to max. 300 mA for the encoder, this current also loads the +5V bus on the module