Saia-Burgess Controls AG
Manual I/O-modules for PCD1 │ PCD2 series │ Document 27-600 – Release ENG09 │ 2019-05-01
6-51
I/O modules PCD3
PCD3.A860
6
the F-Box, and must be carried out after activation.
Shade function, short move function
If a key (or ext. Input 0 / Input 1) is activated briefly, the corresponding relay
switches on for the "short move time". If the key/input is activated for longer than
the "short move time", the output will stay on for as long as the key is pressed.
During a short move, the relay cannot be interrupted by any further input or key
activation on the module.
Input
Output
Input
Output
short move time
short move time
Shade function, hold function
If a key (or Input 0 / Input 1) is activated for longer than the defined "hold time",
the module will switch to hold operation. The smallest value that can be set for the
hold time is 1 (1/10 second), i.e. the module will switch directly into hold mode.
In hold mode, the output (blinds up/down) stays on for the defined "move time".
The module resets the output at the end of this time. The movement can be
stopped by activating an input. The processing of these times may be affected by
accesses by the Saia PCD
®
. The hold function can also be activated via the FBox.
Input
Output
> hold-time
move-time
short move-time
Stopping the movement
If an output is switched to hold mode, this will stop as soon as a new input pulse is
detected, regardless of which key (direction) is pressed.
Input
Output
> hold-time
move-time
Input
Ø
oder 1