Saia-Burgess Controls AG
Manual I/O-modules for PCD1 │ PCD2 series │ Document 27-600 – Release ENG09 │ 2019-05-01
9-8
PCD2.G200
Preparing the PLC system
9
9.3.2.1.2 Con
fi
guring Analog Inputs
The Media Mapping for analog inputs and outputs has to be set to Yes:
Figure 7: Mapping Analogues Inputs
For each analog input there are several resolution options to select :
Analog inputs 0 and 1 can be set to 0…
10000 mV or user defined range or to non
converted 12 bit values 0…4095:
Figure 8: Range selection AI0 / AI1
The default user range is 0…1000
The Analog Inputs 2 to 5 (with the DIP switches) havethe following possibilities:
Figure 9: Range selection AI2…AI5
There is no automatic recognition when uploading the configuration from the CPU
since the DIP switch position can not be read by the CPU.
For the Analog Inputs 6 and 7 there are the following options:
Figure 10: Range selection AI6 / AI7